BOLD Industrial
Fluke 377FC True-RMS Non Contact Clamp Meter
Couldn't load pickup availability
Fluke 377 FC – Specifications
⚡ Electrical Measurements
-
AC Current (Clamp Jaw)
-
Range: Up to 999.9 A
-
Resolution: 0.1 A
-
Accuracy: ±2% ±5 digits (10–100 Hz), ±2.5% ±5 digits (100–500 Hz)
-
Crest Factor: Up to 3 (varies with current range)
-
-
AC Current (iFlex Flexible Current Probe)
-
Range: Up to 2500 A
-
Resolution: 0.1 A to 1 A
-
Accuracy: ±3% ±5 digits (5–500 Hz)
-
-
DC Current (Clamp Jaw)
-
Range: Up to 999.9 A
-
Resolution: 0.1 A
-
Accuracy: ±2% ±5 digits
-
-
AC Voltage (FieldSense, Non-Contact)
-
Range: Up to 1000 V
-
Accuracy: ±3% ±5 digits (typical for conductors up to 4/0 AWG)
-
-
AC/DC Voltage (Test Leads)
-
Range: Up to 1000 V
-
Resolution: 0.1 V (≤600 V), 1 V (≤1000 V)
-
Accuracy: ±1% ±5 digits
-
-
DC mV Input
-
Range: Up to 500.0 mV
-
Resolution: 0.1 mV
-
Accuracy: ±1% ±5 digits
-
-
Frequency (Clamp or iFlex)
-
Range: 5 Hz to 500 Hz
-
Resolution: 0.1 Hz
-
Accuracy: ±0.5% ±5 digits
-
-
Resistance
-
Range: Up to 60 kΩ
-
Resolution: 0.1 Ω / 1 Ω / 10 Ω
-
Accuracy: ±1% ±5 digits
-
-
Capacitance
-
Range: Up to 1000 µF
-
Resolution: 0.1 µF to 1 µF
-
Accuracy: ±1% ±4 digits
-
🛠 Features
-
FieldSense™ Technology: Non-contact measurement of voltage and current
-
iFlex Probe: Expands current measurement range to 2500 A AC
-
Three-Phase Testing: Complete 3-phase voltage and current measurement in 3 quick steps
-
Fluke Connect Compatible: Wireless logging, remote monitoring, and reporting
-
Visual Continuity & Measurement Stability Indicators: Visual cues for live circuits and stable readings
-
Data Hold, Auto Power-Off, Min/Max/Avg Recording
📐 Physical & General Specs
-
Jaw Opening: 34 mm
-
iFlex Probe: 1.8 m length, 7.5 mm diameter, 450 mm Rogowski coil
-
Display: Dual-display for simultaneous measurement readouts
-
Battery: 2 × AA batteries
-
Battery Life: ~200 hours
-
Dimensions: 274 × 86 × 47 mm
-
Weight: Approx. 463 g
🌍 Environmental & Safety Ratings
-
Operating Temperature: –10 °C to +50 °C
-
Storage Temperature: –40 °C to +60 °C
-
Humidity: 0%–90% RH (non-condensing up to 30 °C)
-
Altitude: Operating up to 2000 m
-
Ingress Protection: IP30 (with jaw closed)
-
Safety Category Ratings: CAT III 1000 V / CAT IV 600 V
-
Pollution Degree: 2
✅ Summary Table
Function | Range / Accuracy |
---|---|
AC Current (Clamp) | Up to 999.9 A / ±2% ±5 digits |
AC Current (iFlex) | Up to 2500 A / ±3% ±5 digits |
DC Current | Up to 999.9 A / ±2% ±5 digits |
Voltage (AC/DC) | Up to 1000 V / ±1% ±5 digits |
FieldSense Voltage | Up to 1000 V / ±3% ±5 digits |
Resistance | Up to 60 kΩ / ±1% ±5 digits |
Capacitance | Up to 1000 µF / ±1% ±4 digits |
Frequency | 5–500 Hz / ±0.5% ±5 digits |
Display | Dual, backlit |
Power Supply | 2 × AA batteries |